| Capacity Specifications for the LCR |
| MODEL |
1354-A |
1354-B |
1465-A |
1465-B |
1665-A |
1665-B |
1865-A |
1865-B |
2162-A |
2162-B |
2472-A |
| Capacity/Lbs. of Salt |
Maximum |
75,000/ 38 |
75,000/ 38 |
90,000/ 45 |
90,000/ 45 |
120,000/ 60 |
120,000/ 60 |
150,000/ 75 |
150,000/ 75 |
210,000/ 105 |
210,000/ 105 |
300,000/ 150 |
| Medium |
65,000/ 23 |
65,000 /23 |
78,000/ 27 |
78,000/ 27 |
104,000/ 36 |
104,000/ 36 |
130,000/ 45 |
130,000/ 45 |
182,000/ 63 |
182,000/ 63 |
260,000/ 90 |
| Minimum |
50,000/ 15 |
50,000/ 15 |
60,000/ 18 |
60,000/ 18 |
80,000/ 24 |
80,000/ 24 |
100,000/ 30 |
100,000/ 30 |
140,000/ 42 |
140,000/ 42 |
200,000/ 60 |
| Type of Media |
Resin |
Resin |
Resin |
Resin |
Resin |
Resin |
Resin |
Resin |
Resin |
Resin |
Resin |
| Iron & Mang. Capacity(1) |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
| pH Capacity(2) |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
| Continuous @ 15 PSI Pressure Drop(3) |
18 |
29 |
19 |
30 |
20 |
33 |
20 |
35 |
20 |
39 |
21 |
| Peak @ 25 PSI Pressure Drop(3) |
25 |
40 |
26 |
42 |
27 |
45 |
27 |
48 |
27 |
52 |
28 |
| Mineral Quantity (Cu. Ft.) |
2.5 |
2.5 |
3 |
3 |
4 |
4 |
5 |
5 |
7 |
7 |
10 |
| Backwash Rate (GPM)(4) |
3.5 |
3.5 |
5 |
5 |
6 |
6 |
8 |
8 |
12 |
12 |
15 |
| Pipe Size |
1" |
1.5" |
1" |
1.5" |
1" |
1.5" |
1" |
1.5" |
1" |
1.5" |
1" |
| Shipping Weight(5) |
230 |
245 |
290 |
305 |
365 |
380 |
460 |
475 |
665 |
680 |
910 |
| Tank Size |
Media Tank |
13"(w) x 54"(h) |
13"(w) x 54"(h) |
14"(w) x 65"(h) |
14"(w) x 65"(h) |
16"(w) x 65"(h) |
16"(w) x 65"(h) |
18"(w) x 65"(h) |
18"(w) x 65"(h) |
21"(w) x 62"(h) |
21"(w) x 62"(h) |
24"(w) x 72"(h) |
| Brine Tank |
18"(w) x 40"(h) |
18"(w) x 40"(h) |
18"(w) x 40"(h) |
18"(w) x 40"(h) |
24"(w) x 41"(h) |
24"(w) x 41"(h) |
24"(w) x 41"(h) |
24"(w) x 41"(h) |
24"(w) x 50"(h) |
24"(w) x 50"(h) |
30"(w) x 50"(h) |
|
Notes: Resin Capacities based on industry
standards. CR-100 and CR-200 interpolated from the ASC Series
Water Conditioners.
|
|
(1) On waters that are prechlorinated or where other preoxidation occurs, iron or manganese can precipitate too small to be filtered.
(2) The pH of the influent water must be at least the specified number above. pH correction is dependent upon flow rate.
(3) Quality of water may vary depending
upon flow rate and water conditions.
(4) Backwash rates may change depending on temperatures
of water.
(5) Shipping weight is dry. |
1900 Prospect Court • Appleton, WI • Phone: (920) 739-9401 • Fax: (920) 739-9406
©2004 Water-Right, Inc.
|